1.Features:
- Being able to be directly welded on PCB;
- Fully encapsulated, strong mechanical and environmental endurance, strong
dielectric strength and beautiful appearance.
2.Conditions of usage:
- Circumstance temperature: -55...+85°C;
- Relative humid <90% при 40°C;
- Atmospheric pressure: 860~1060mbar (650~800mmHg approximately);
3.Range of working Frequency: 20Hz~1kHz
4.Insulation Rating: Class F (155°C).
5.Safety features:
- Insulation resistance: >1000MOm in normal condition;
- Insulation withstand voltages: 6000V 50Hz/1min;
- Fire proof: accord with the grade of UL94-Vo
6.Outline Drawing, Installation Dimention and Coil Diagram
7.Typical Usages and Technical Parameters.
1) The parameters are listed in Table 1 while the sampling voltage is obtained
directly by using a resistor (as shown in Fig.1 below).
2) The parameters are listed in Table 2 while the sampling voltage is obtained
by using an IC (as shown in Fig.2 below).
Table 1
Model |
Rated
Input
current |
Rated
Output
current |
Rated
sampling
resistance |
Rated
sampling
voltage |
Phase
Shift |
Non
Linearity |
Linear
Range |
Withstand
Voltage |
TA250-1 |
100A |
100mA |
100 Om |
8V |
<30` |
<1% |
>2.5
times
of
rated
value |
>6kV |
TA250-2 |
100A |
50mA |
200 Om |
16V |
TA250-3 |
100A |
33.3mA |
300 Om |
24V |
TA250-4 |
100A |
25mA |
400 Om |
30V |
TA250-5 |
100A |
20mA |
500 Om |
40V |
Table 2
Model |
Rated
Input
current |
Rated
Output
current |
Rated
sampling
voltage |
Phase
Shift |
Non
Linearity |
Linear
Range |
Withstand
Voltage |
TA250-1 |
100A |
100mA |
<1/2
times
of IC
power
supply |
<10` |
<0.2% |
>2.5
times
of
rated
value |
>6kV |
TA250-2 |
100A |
50mA |
TA250-3 |
100A |
33.3mA |
TA250-4 |
100A |
25mA |
TA250-5 |
100A |
20mA |
8.Attention:
- The primary of the current transformer must be connected in series with the
loop of the measured current. The secondary should operate in a mode of near short
circuit.
- The secondary of the current transformer is not allowed to be open circuit,
Do Not install any fuse.
|